Micro-controller unit based ■ Real time processing / High precision ■ Protections : Over current, Under current, Phase loss, Phase reversal, Stall, Jam, Current Imbalance, Earth fault (3MZ2/FMZ2) ■ Inverse available up to 32Amps without external CTs. ■ Ancillary functions : Fail safe, Pre-alarm (3DM2/FDM2), Accumulated running hour, 3 faults records & limitation of auto-restart. ■ Reinforced monitoring function : Monitoring distance up to 400M, 3 phase current display, Pre-alarm (3DM2/FDM2) & Trip cause indication ■ Bar graph indication of a load current to the current setting. ■ Available application on single and 3 phase motor ■ RoHS Compliance ■ For FDM2/FMZ2, normal protections are guaranteed even if PDM is disconnected. | |
 |
|
|
|
 |
|
|
Protective Item |
Condition & Setting range |
Operation time |
|
Over-current |
Condition : Load current (In) exceeds setting current (Is) Setting range : 0.5~60A (Def), 0.5~32A (Inv)
|
Definite (Def) : 0.2~30s adjust. Inverse (Inv) : 1~30 class |
|
Under-current |
Condition : Load current (In) less than setting currentIn ≤ uc uc should be less than oc setting
|
oFF, 1~10s adjustable |
|
Reverse phase (RP) |
Condition : Reversed phase sequence input on EOCR. Enable or disable : Selectable
|
Within 0.15s |
|
Stall (Sc) |
Condition : In ≥ Stall current setting (Sc). Active only in motor starting 0.5~30A : 2~8 times of oc setting ~40A : 2~6 times, ~60A : 2~4 times.
|
Right after D-time elapsed |
|
Jam (JA) |
Condition : In ≥ Jam current setting (JA). Active only in motor running 0.5~50A : 1.5~5 times of oc setting ~60A : 1.5~4 times of oc setting
|
0.3~5s adjustable |
|
Imbalance (IM) |
Condition : Current imbalance ≥ Setting imbalance % Setting range : 10~50% of imbalance
|
1~10s adjustable |
|
Earth fault (EF) |
Condition : EF current (Ie) exceeds setting current (Ies) OFF, 0.03~10A
|
0.05~5s adjustable -- 3MZ2/FMZ2 only --
|
|
|
 |
|
|
Over current |
Rated setting range (A) |
Definite TCC : 0.5~60A : use external CT higher than 60A |
|
|
Inverse TCC : 0.5~60A : use external CT higher than 32A |
|
Under current |
Rated setting range (A) |
0.5A ~ less than oc setting |
|
Operating time characteristics |
Definite(Def) / Inverse(Inv) |
|
Time Setting |
Def |
D-time |
0~200s |
|
O-time |
0.2~30s |
|
Inv (cLS) |
1~30 classes |
|
GF delay time (Edt) |
0~30s (3MZ2/FMZ2) |
|
GF O-time (Et) |
0.05~10s (3MZ2/FMZ2) |
|
Auto-reset |
0.5s~20min. |
|
Reset mode |
Manual reset (H-r) / Electric reset (E-r) / Auto-reset (A-r) |
|
Control power |
Voltage |
100~240VAC/DC (85% ~110%, Free voltage), 24VAC/DC ( ±5%) . |
|
Frequency |
50/60Hz |
|
Power consumption |
Lower than 7VA |
|
Output |
Capacity |
3A/250VAC resistive. |
|
Composition |
1a1b : OC or GR |
|
1a : AL |
|
Display |
7 segment LED |
3 phase amps, Cause of trip, Setting parameters indication. |
|
Bar-graph |
Load factor. |
|
Mounting |
Panel mounting (3DM2/3MZ2) |
|
Flush mounting (FDM2/FMZ2) |
|
Insulation |
Between case & circuit |
Over DC500V 10MΩ |
|
Dielectric strength |
Between case & circuit |
2kV, 50/60Hz, I Min. |
|
Between contacts |
1kV, 50/60Hz, I Min. |
|
Between circuit |
2kV, 50/60Hz, 1 Min |
|
Electrostatic discharge (ESD) |
IEC61000-4-2 |
Level 3 : Air discharge : ±8kV, Contact discharge : ±6kV |
|
Radiated disturbance |
IEC61000-4-3 |
Level 3 : 10V/m, 80 ~ 1000MHz |
|
Conducted disturbance |
IEC61000-4-6 |
Level 3 : 10V,0.15 ~ 80MHz |
|
EFT/Burst |
lEC61000-4-4 |
Level 3 : ±2kV, 1 Min. |
|
Surge |
IEC61000-4-5 |
Level 3 : 1.2 x 50μs, ±4kV (0°, 90°, 180°, 270°) |
|
Emission |
CISPR11 |
Class A ( Conducted and radiated) |
|
Environment |
Temperature |
Store |
-40°C ~ +85°C |
|
Operation |
-20°C ~ +60°C |
|
Humidity |
30~85% RH (Non-condensate) |
|
Weight |
|
3DM2 / 3MZ2 |
FDM2 / FMZ2 |
|
Window type |
265g |
350g |
|
Bottom hole type |
295g |
390g |
|
Terminal type |
295 + 120 = 415g |
390 + 120 = 510g |
|
Display (W/3M cable) |
|
125g |
|
Power consumption |
Less than 7VA. | | |
|
| | |